Free Match Series R410A GMV Multi VRF System-Outdoor Unit (For European Union)
Applicable models: AM5O-120HPDC1 AM5O-12 0HPDC1
Please read this manual carefully before the installation and operation of this product.
User Notice ◆ The total capacity of the indoor units which runs at the same time can not exceed 150% of that of the outdoor units; otherwise, the cooling (heating) effect of each indoor unit would be poor.
◆ Switch the main power on 8 hours before start the unit, helpful for a successful startup. ◆ It is a normal phenomenon that the indoor unit fan will still run for 20~70 seconds after the indoor unit receives the “stop” signal so as to make full use of after-heat for the next operation.
◆ When the running modes of the indoor and outdoor units conict, it will be indicated on the display of the wired controller in ve seconds and then the indoor unit will stop. In this case, they can back to the normal condition by harmonizing their running modes: the cooling mode is compatible with the dehumidifying mode and the fan mode can go with any other mode. If the supply power fails when the unit is running, then the indoor unit will send the “start” signal to the outdoor unit three minutes later after power recovery.
◆ During installation, the communication cable and the power cord must not be twisted together but instead separated with an interval of at least 2cm; otherwise the unit is likely to run abnormally.
◆ Cautions for the Debugging and Maintenance Personnel: During debugging and maintenance, prior to the startup of the compress make sure the heating belt of the compressor has been energized for at least eight hours! Once the compressor is started, it must be guaranteed that it works continuously for at least 30 minutes, otherwise it would be damaged! This series outdoor units are matched with the free macth series R410A GMV multi VRF indoor units under the same working conditons exported to European Union. This product must not be disposed together with the domestic waste. This product has to be disposed at an authorized place for recycling of electrical and electronic appliances.
Thank you for purchasing ALPICAIR air conditioners. Before use, please read this manual carefully and keep it properly for further reference.
Contents ....................................................................................... ............................................. 1 Ⅰ Safety Precautions.......................................... ............................................................................... ..................................... 2 Ⅱ Installation Instructions.......................................... 1 Installation Location Location and Matters Needing Needing Attention............................... .......................................... ........... 2 2 Installation of the Outdoor Unit................................ ................................................................ ........................................... ........... 4 3 Connection between Indoor Indoor and Outdoor Units ............................. .................................................. ..................... 6 ........................ ........................ ........................ ........................ ..................... .........8 4 Refrigeran Refrigerantt Charging and Trial Running ............
................................................................. 11 Ⅲ Working Principles of the Unit ................................................................. ............................................................ ................... 12 Ⅳ Parts and Components of the Unit ......................................... ........................................................................................... ................................................... ... 13 Ⅴ Maintenance ........................................... 1 Check before the Seasonal Use ........................... ........................................................... .............................................. .............. 13 2 Check after the Seasonal Use .............................. .............................................................. .............................................. .............. 13
1 Please check the following items before before contact the maintenance serviceman. 14 2 The conditions listed below are not classied into errors. errors................ ...................... .............. ........... .... 15 3 Error description ............................. ............................................................. ................................................................ ................................... ... 15 4 AfterAfter-Sales Sales Service .............................. .............................................................. .............................................................. .............................. 21
Safety Precauti Precautions ons Precautions ons Ⅰ Safety Precauti Please read this manual carefully before use and operate correctly as instructed in this manual. Please especially take notice of the following two symbols: Warning! It indicates improper operation which will lead to human casualty or sever injury. Cuation! It indicates improper operation which will lead to injury or property damage. Warning! ◆ The installation should be committed to the appointed service center; otherwise it all cause water
leakage, electric shock or re etc. ◆ Please install the unit where is strong enough to withstand the weight of the unit; otherwise, the unit would fall down and cause injury or death.
◆ The drain pipe should be installed as instructed in the manual to guarantee the proper drainage; meanwhile it should be insulated to prevent condensing; otherwise the improper installation would cause water leakage and then wet the household wares in the room.
◆ Do not use or place any inammable or explosive substance near the unit. ◆ Under the occurrence of an error (like burning smell etc.), please cut off the main power supply of the unit.
◆ Keep good ventilation in the room to avoid oxygen decit. ◆ Never insert your nger or any other object into the air outlet/inlet grille. ◆ Please take notice of the supporting frame of the unit to see if it is damaged over the long time period of use. ◆ Never ret the unit and contact the sales agent or the professional installation personnel for the repair or relocation of the unit.
◆ Non-professional personnel are prohibited to dismantle the electric box owing to the high voltage of the outdoor unit. An all-pole disconnection switch having a contact separation of at least 3mm in all poles should be connected in fxed wiring. Cuation! ◆ Before installation, please check if the power supply corresponds with the requirement specied on the
nameplate and also check its security.
◆ Before use, please check if the piping and wiring are correct to avoid water leakage, refrigerant leakage, electric shock, re etc. ◆ The main power supply must be earthed to avoid the hazard of electric shock and never connect this earth wire to the gas pipe, running water pipe, lightening rod or phone cable’s earth lead.
◆ Turn off the unit after it runs at least ve minutes; otherwise its service life will be shortened. ◆ Do not allow children operate this unit. ◆ Do not operate this unit with wet hands. replace ment of the air lter. ◆ Cut off the main power supply prior to the cleaning of the unit or the replacement
◆ When the unit is not to be used for a long time, please cut off the main power supply of the unit. ◆ Do not expose the unit to the moist or corrosive circumstances. ◆ Never step on the unit or place any object on it. ◆ It is suggested to have a power-on test annually.
1
Installation Instructions
Ⅱ Installation Instructions 1 Installation Location and Matters Needing Needing Attention The installation of the unit must comply with the national and local safety regulations. The installation quality directly affects the normal use, so the user should not carry out the installation personally.. Instead, the installation and debugging should be done by the professional personnel. personally Only after that, can the unit be energized. a. How to select the installation location for for the indoor unit 1) Where there is no direct sunlight. 2) Where the top hanger, hanger, ceiling and the building structure are strong enough to withstand withstand the weight of the unit. 3) Where the drain pipe can be easily connected to outside. 4) Where the ow of the air inlet/outlet is not blocked. 5) Where the refrigerant pipe of the indoor unit can be easily led to outside. 6) Where there is no inammable, explosive substances or their leakage. 7) Where there is no corrosive gas, gas, heavy dust, salt mist, smog smog or moisture. b. How to select the installation location for for the outdoor unit 1) The outdoor unit must be installed where where the bearing surface is stable and secure secure enough. 2) The outdoor unit and indoor unit should be placed as close as possible to minimize the length and bends of the refrigerant pipe. 3) Do not install the outdoor unit under the window or between between the buildings to prevent the normal running noise entering the room. 4) Where the ow of the air inlet/outlet is not blocked. 5) The outdoor unit should be installed where ventilation is in good condition so that the unit can take in and discharge enough air. 6) Do not install the unit where there are inammable and explosive substances and where where there is heavy dust, salt fog and other severely polluted air. No air guiding pipe is allowed to be installed at the air inlet/outlet of the outdoor unit. Under the heating mode, the condensate water would drip down from the base frame and would be frozen when the outdoor ambient temperature is lower than 0℃(32 ℉). Besides, the installation of the outdoor unit should not affect the heat radiation of the unit. CUATION ! The unit installed in the following places is likely to run abnormally. If unavoidable, please contact the
professional personnel at the GREE appointed service center. ① where is full of oil; ② alkaline soil off the sea; ③ where there is sulfur gas(like sulfur hot spring); ④ where there are devices with high frequency (like wireless devices, electric welding devices, or medical equipments); ⑤ special circumstances. c. Electric Wiring 1) The installation must be done in accordance with with the national wiring regulations. 2) Only the power cord with the rated voltage and exclusive circuit for the air conditioning can be used. 3) Do not pull the the power cord by force. 4) The electric installation should be carried out by the professional professional personnel as instructed by the local laws, regulations and also this manual. 5) The diameter of the power cord should be large large enough and once it is damaged it must be replaced by 2
Installation Instructions the dedicated one. 6) The earthing should be reliable and the earth wire should should be connected to the dedicated device of the building by the professional personnel. Besides, the air switch coupled with the leakage current protection switch must be equipped, which is of enough capacity and of both magnetic and thermal tripping functions in case of the short circuit and overload. Table 1 Models
d. Earthing Requirements 1) The air conditioner is classied into the the Class I appliances, so its earthing must be reliable. 2) The yellow-green line of the air conditioner is the earth line and can not be used used for other purpose, cut off or xed by the self-tapping screw; otherwise it would cause the hazard of electric shock. 3) The reliable earth terminal should should be provided and the earth wire can not be connected to any of the following places. ① . Running water pipe; ② . Coal gas pipe; ③ . Sewage pipe; ④ . Other places where the professional personnel think unreliable. AM5O-120HPDC1 AM5O-120 HPDC1 I N D O O R U N I T E
XT6
I N D O O R U N I T D
XT5
N I D O O R U N I T C
XT4
I N D O O R U N I T B
XT3
I N D O O R U N I T A
XT2
O U T D O O R U N I T
L
N
POWER
XT1
Fig.1 3
Installation Instructions e. Noise Precautions 1) The air conditioning unit should be installed installed where ventilation is in good condition, otherwise otherwise the working capability of the unit would be reduced or working noise would be increased. 2) The air conditioning unit should be installed on the base frame which is stable stable and secure uncouth to withstand the weight of the unit; otherwise it would incur vibration and noise. 3) During the installation, a consideration should be taken that the produced hot air or noise should not affect neighbors and surroundings. 4) Do not stack obstacles near the air outlet of the outdoor unit; otherwise it would reduce reduce the working capability of the unit or increase the working noise. 5) In the event of the occurrence of abnormal noise, please contact the sales agent as soon as possible. possible. f. Accessories for Installation Refer to the packing list for the accessories of the indoor and outdoor units respectively.
2 Installation of the Outdoor Unit a. Precautions for the Installation of the Outdoor Outdoor Unit The following rules should be followed when the installation location is being considered so as to let the unit run well enough. 1) The discharged air from the outdoor unit won’t return back and enough space should be left for maintenance around the unit. 2) The installation location should be in good condition so that the unit is able to take in and discharge discharge enough air. Besides, make sure there is no obstacle at the air inlet/outlet of the unit. If there is, remove it. 3) The unit must be installed where it is secure enough to support the weight of the unit and capable of reducing to some extent noise and vibration to make sure they do not bother your neighbors. 4) The designated lifting hole must be used for lifting the unit and protect the unit carefully during during lifting to prevent damaging the mental sheet which would result in rusting in future. 5) The unit should be installed where there is as little as direct sunlight. 6) The unit must be installed where the rain water and defrosting water can be drained. 7) The unit must be installed where the unit won’t won’t be covered by the snow and won’t be affected by rubbish and oil fog. 8) Rubber or spring shock absorbers should be used during the installation installation of the outdoor unit to meet the noise and vibration requirements. 9) The installation dimensions should meet the requirement covered in this manual and the outdoor unit must be xed securely securely.. 10) The installation should be carried out by the professionally skilled personnel. b. Installation of the Outdoor Unit 1) Outline Dimension of the Outdoor Unit.
4
Installation Instructions AM5O-120HPDC1 1087 1015
3 0 1 1
0 5 4
9 9
0 1 4 0 4 4
2 6 6 3 7 1 2 1
631
191
Fig. 4
2) During the transportation of the outdoor unit, two lifting ropes long enough must be used in four directions and the separation angle must be less than 40°prevent the center of unit deviating. 3) During the installation, M12 screws screws should be used to x the the support leg and base frame of the unit. 4) The unit should be installed on a concrete base frame with a height of 10cm. 5) The installation space of the unit should be as required in Fig.5. Installation Space Requirements of the Outdoor Unit: AM5O-120HPDC1 >1000
0 0 5 >
>500
>2000
0 0 5 >
>500
>2000
Fig.5
3 Connection between Indoor and Outdoor Units a. Wiring of the Power Power Cord CUATION ! A breaker must be installed, capable of cutting off the power supply for the whole system.
1) Open the side plate. 2) Let the power cord go through the rubber ring. 3) Connect the power card card to the terminals “L”, “N” and also also the earthing bolt, and then connect connect the wiring terminals “N(1),2,3” of the indoor unit to those of the outdoor unit correspondingly correspondingly.. 4) Fix the power cord with wire wire clips. 5
Installation Instructions b. Capacity Level and Capacity Code of the Indoor and Outdoor Units Table 2 Capacity Level
Capacity Code
09
25
12
35
18
50
21
60
24
71
36
100
42
120
Indoor Unit
Outdoor Unit
1) The outdoor unit with capacity level 36 can drive up to four sets of indoor units, while the outdoor unit 42 can drive up to ve. 2) The sum of the capacity codes of the indoor units should be among 50%-150% of that of the outdoor unit. c. Allowable Length and Height Fall of the Refrigerant Pipe Table 3 Allowable Length
Refrigerant Pipe
36
42
36
42
Total Length(m)
70
80
L1+L2+L3+ L4
L1+L2+L3+ L4+ L5
Max. Length for Single Unit(m)
20
25
LX
Outdoor unit and indoor unit
15
15
H1
Indoor unit and indoor unit
7.5
7.5
H2
Max. installation altitude
Table 4: Dimension of the Refrigerant Pipe of the Indoor Unit
unit:mm
Capacity Level of the Indoor Unit
Gas Pipe
Liquid Pipe
09,12
φ9.52
φ6.35
18
φ12.7
φ6.35
21,24
φ15.9
φ9.52
d. Piping between the Indoor and Outdoor Units 1) Refer to Fig.6 for the moments of torque for tightening screws. 2) Let the are end of the copper pipe point at the screw and then tighten the screw by hand. 3) After that, tighten the screw by the torque wrench unit it clatters (as shown in Fig.6). 4) The bending degree of the pipe can not be too small; otherwise it will crack. And please use a pipe bender to bend the pipe. 5) Wrap the exposed refrigerant pipe and the joints by sponge and then tighten them with the plastic tape.
6
Installation Instructions
Flare Nut
Pipe
Pipe
Torque Wrench
Ordinary
Fig. 6 Table 5:Moments of Torque for Tightening Screws Diameter
Wall Thickness(mm)
Moment of Torque
φ6.35mm
≥ 0.5
15-30( N·m)
φ9.52mm
≥ 0.71
30-40(N·m)
φ12.7mm
≥1
45-50(N·m)
φ15.9mm
≥1
60-65(N·m)
CUATION ! ① . During the connection of the indoor unit and the refrigerant pipe, never pull any joints of the indoor
unit by force; otherwise the capillary pipe or other pipe may crack, which then would result in leakage. ② . The refrigerant pipe should be supported by brackets, that is, don’t let the unit withstand the weight of
it. CUATION ! For the GMV multi VRF system, each pipe should be labeled to tell which system it belongs to avoid
mistaken inaccurate piping. e. Installation of the Protection Layer of the Refrigerant Pipe 1) The refrigerant pipe should be insulated by the insulating material and plastic tape in order to prevent condensing and leaking. 2) The joints of the indoor unit should be wrapped with the insulating material and no gas is allowed on the joint of the indoor unit, as shown in Fig.7.
No gap
Fig.7
!
CUATION After the pipe is protected well enough, never bend it to form a small angle; otherwise it would crack or
break. f. Wrapping the pipe with tape 7
Installation Instructions 1) Bundle the refrigerant pipe and electric wire together with tape, and separate them from the drain pipe to prevent the condensate water overowing. 2) Wrap the the pipe from the bottom of the outdoor unit unit to the top of the pipe where it enters the the wall. During the wrapping, the later circle should cover half of the former one. 3) Fix the wrapped pipe on the wall with with clamps. CUATION ! ① . Do not wrap the pipe too tightly; otherwise the insulation effect would be weakened. Additionally,
make sure the drain hose is separated from the pipe. ② . After that, ll the hole on the wall with sealing material to prevent wind and rain coming into the room.
4 Refrigerant Charging Charging and Trial Trial Running a. Refrigerant Charging 1) The refrigerant has been charged into the outdoor unit before shipment, while additional refrigerant still need be charged into the refrigerant pipe during the eld installation. 2) Check if the liquid valve and the gas valve of the outdoor unit are closed fully. fully. 3) As shown in the following following gure (Fig.8), expel the gas inside the indoor unit and refrigerant pipe out by the vacuum pump. Manometer
Manometer “HI” knob
“LO” knob
Vacuum pump
Hose Gas Valve
Fig.8 4) When the compress is not running, charge the R410A refrigerant into the refrigerant pipe from the liquid valve of the outdoor unit (do not do it from the gas valve). b. Calculation of the Additional Refrigerant Charge Charge 1) Refrigerant Charge in the Outdoor Unit before Shipment Table 6 Model
AM5O-120HPDC1 AM5O-120HPD C1
Refrigerant Charge (kg)
4.8
Notes: ① . The refrigerant charge mentioned in the table above is not included those charged additionally in the
indoor unit and the refrigerant pipe. ② . The amount of the additional refrigerant charge is dependent on the diameter and length of the liquid
refrigerant pipe which is decided by the actual yield installation requirement. ③ . Record the additional refrigerant charge for future maintenance. 2) Calculation of the Additional Refrigerant Charge Charge
If the total refrigerant pipe length (liquid pipe) is smaller than that listed in the table below, no additional 8
Installation Instructions refrigerant will be charged. Table 7 Model
Total Liquid Pipe Lenght (a+b+c+d+e)
≤ 50m
AM5O-120HPDC1
Additional Refrigerant Charge2=∑Extra Liquid Pipe Length×22g/m(liquid pipe 1/4’ 1/4’’’). Note: if the total refrigerant pipe length is larger than that listed in the table above, the additional refrigerant for the extra length of the pipe needs to be charged as per 22g/m. 3) Example : AM5O-120HPDC1
e d c b a Fig.9 Table 8 Indoor Unit Serial No.
Model
Indoor Unit ⑤
Ducted Type ATMI-26HPDC1
Indoor Unit ④
Ducted Type ATMI-26HPDC1
Indoor Unit ③
Ducted Type ATMI-26HPDC1
Indoor Unit ②
Ducted Type ATMI-26HPDC1
Indoor Unit ①
Ducted Type ATMI-53HPDC1
Table 9 Liquid Refrigerant Pipe Serial No.
e
d
c
b
a
Diameter
φ6.35
φ6.35
φ6.35
φ6.35
φ9.52
Length
20m
20m
15m
5m
5m
The total length of each liquid refrigerant pipe is: e+d+c+b+a=20+20+15+5+5=65m. Thus, the minimum additional refrigerant charge=(65-50)×0.022=0.33kg (Note: no additional refrigerant is needed for the liquid pipe within 50m). 4) Additional Refrigerant Charge Record Table 10 Indoor Unit No.
c. Items to be checked after the Installation Table 12 Items to be Checked
Possible Errors
Has each part and component the the of unit installed securely?
The unit may fall off, vibrate or generate noise. The cooling (heating) capacity may be poor.. poor
Has the gas leakage test been taken? Is the thermal insulation sufcient?
Dews and water drops may be generated.
Does the drainage go well?
Dews and water drops may be generated.
Is the actual power voltage in line with the value marked on the nameplate?
The unit may break down or some components may be burnt out.
Are the wiring and the piping correct?
The unit may break down or some components may be burnt out.
Has the unit be been en ea eart rth hed re rellia iabl bly y?
Ther Th eree may may be a dan dang ger of ele lecctr triic sho shock ck..
Does the wire meet the regulated requirement?
The unit may break down or the component may be burnt out.
Is there any obstacle at the air inlet/outlet of the indoor/outdoor unit?
The cooling (heating) capacity may be poor
Have the length of the refrigerant pipe and the refrigerant charge been recorded?
It may be hard to know the exact refrigerant charge.
Check Results
d. Trial Running 1) Check before the Trial Running ①.
Check if the appearance of the unit and the piping system are damaged during the transportation. ② . Check if the wiring terminals of the electronic component are secure. ③ . Check if the rotation direction of the fan motor is right. ④ . Check if all valves in the system are fully opened.
2) Trial Running ① . The trial running should be carried out by the professionally skilled personnel on the premise that all
items listed above are in normal conditions. ② . Let the unit energized and switch the wired controller or the remoter controller to “ON”. ③ . The fan motor and compressor of the outdoor unit will run automatically in one minute. ④ . If there is some unusual sound after the compressor is started, turn off the unit for an immediate
check.
10
Working Principles of the Unit
Ⅲ Working Principles of the Unit Schematic Diagram of Free Match Series Inverter Heat Pump Multi VRF System M
Fig. 10 Schematic Diagram of Free Match Series Inverter Inverter Heat Pump Multi VRF System The outdoor and indoor units start to work once the power is switched on. During the cooling operation, the low temperature, low pressure refrigerant gas from the heat exchanger of each indoor unit gets together and then is taken into the compressor to be compressed into high temperature, high pressure gas, which will soon go to the heat exchanger of the outdoor unit to exchange heat with the outdoor air and then is turned into refrigerant liquid. After passing through the throttling device, the temperature and pressure of the refrigerant liquid will further decrease and then go the main valve. After that, it will be divided and go to the heat exchanger of each indoor unit to exchange heat with the air which needs to be conditioned. Consequently, the refrigerant liquid become low temperature, low pressure refrigerant gas again. Such a refrigeration cycle goes round and round to achieve the desired refrigeration purpose. During the heating operation, the four-way valve is involved to make the refrigeration cycle run reversely. The refrigerant radiates heat in the heat exchanger of the indoor unit (so do the electric heating devices) and absorb heat in the heat exchanger of the outdoor unit for a heat pump heating cycle so as to achieve the desired heating purpose.
11
Parts and Components of the Unit
Ⅳ Parts and Components of the Unit System Structure Outdoor Unit
Cassette Type Indoor Unit
Duct Type Indoor Unit(Round air outlet)
Wall Mounted Indoor Unit
Duct Type Indoor Unit(Rectangular air outlet)
Fig. 11 For the free match series DC inverter GMV multi VRF air conditioning system, one outdoor unit is able to drive up to ve indoor units which can be cassette type, duct type, wall-mounted or oor ceiling type. Among them, the cassette type and the wall-mounted indoor units should be controlled by the remote controller, while the ducted type can be controlled by either the remote controller or the wired controller. The outdoor unit will run as long as any one indoor unit receives the running command, and all indoor units stops once the outdoor units is turned off.
12
Maintenance Ⅴ Maintenance WARNING ! ① . The unit can only be cleaned after the unit is turned off and the main power is cut off; otherwise it
would cause an electric shock hazard. ② . Do not dampen the air conditioner, as it would cause a electric shock hazard and never rinse the unit
with water in any event. CUATION ! ① . Volatile liquid, like thinner, gasoline etc would damage the appearance of the air conditioning unit. (Only use the soft dry cloth or the wet cloth with neutral detergent clean the outer shell of the air conditioning
unit) ② . Do not clean the outer shell of the air conditioning unit with more than 45 ℃ hot water to prevent
discoloration or deformation. ③ . Do not dry the air lter screen of the indoor unit on the re to prevent inammation or deformation.
1 Check before before the Seasonal Use 1) Check if the inlet/outlet inlet/outlet of the indoor/outdoor unit is clogged. 2) Check if the earth earth lead is earthed reliably reliably.. 3) Check if the batteries batteries of the remote controller are replaced. 4) Check if the air lter screen is installed improperly. improperly. 5) Check if the installation of the outdoor is secure. If there is something abnormal, please contact the GREE appointed service center. 6) When restarting the unit which is not used for a long time, switch on the main power supply eight hours ahead, helpful for a successful startup.
2 Check after the Seasonal Use 1) Clean the lter screen and body of the indoor and outdoor units. 2) Cut off the main power power supply of the air conditioning system. system. 3) Remove the dust and the foreign matters of the outdoor unit. 4) In the event of rusting, use the anti-rust paint to stop spreading of rust. Refer to the In st stal al la lati ti on an and d Op er erat at io n Ma nu nual al of each indoor unit respectively for detailed maintenance.
13
Troubleshooting Ⅵ Troubleshooting WARNING ! ① . In the event of abnormal conditions (like, stinky smell), please shut off the main power supply
immediately and then contact the GREE appointed service center; otherwise the continuous abnormal running would damage the air conditioning unit and also would cause electric shock or re hazard etc. ② . Do not repair the air conditioning personally but instead contact the professionally skilled personnel
at the GREE appointed service center, as the incorrect repair would cause electric shock or re hazard etc.
1 Please check the following following items before contact contact the maintenance serviceman. serviceman. Table 13 Conditions
The unit does not run
The unit stops soon after it starts
Causes
Corrective Actions
Broken fuse or opened breaker
Change the fuse or close the breaker
Power off
Restart the unit when power on
Loosened power supply plug.
Plug the power supply properly.
Insufcient batteries voltage of the remote controller
Change new batteries
Remoter controller out of the control scope
Keep the control distance within 8 meters.
Clogged inlet/outlet of the indoor/outdoor unit
Clear the obstacle
Clogged inlet/outlet of the indoor/outdoor unit
Clear the obstacle
Improperly set temperature
Adjust the setting of the remote or wired controller.
Too low set fan speed
Adjust the setting of the remote or wired controller. Adjust the setting of the remote
Incorrect air direction Cooling/Heating is abnormal
or wired controller. Opened door and window
Close the door and window
Direct sunlight
Hang a curtain or blinds over the window.
Too much people in the room Too mu much ch he heat at so sour urce cess in th thee roo room m
Redu Re duce ce th thee hea heatt sou sourc rces es
Dirty lter screen
Clean the lter screen
Note:
If the air conditioner still runs abnormally after the above check and handling, please contact the maintenance serviceman at the local appointed service center and also give a description of the error occurred as well as the model of the unit.
14
Troubleshooting 2 The conditions listed listed below are are not classifed into errors Table 14 Conditions
The unit does not run
The un unit it blo blows ws out mis mistt
The unit generates noise
The unit blows out dust. The unit emits odors.
Causes
When restart the unit soon after it is stopped.
The overload protection switch of the unit let the startup delayed for three minutes.
As soon as power is on.
The unit will stand by for approximate one minute. The hi-humidity air indoor is cooled
When Wh en the the coo coolin ling g oper operati ation on sta starts rts.. The unit “clatters” as soon as it starts running.
quickly. It is the sound generated during the initialization initializati on of the electronic expansion valve.
The unit “swishes” during the cooling operation.
It the sound when the refrigerant gas runs inside the unit.
The unit “swishes” when it is started or stopped.
It is the sound when the refrigerant gas stops running.
The unit “swishes” when in it is and after the running.
It is the sound when the draining system is operating.
The unit “squeaks” when it is in and after the running.
It is the sound of frication generated by the skin plate etc which swells due to the temperature change.
When the unit restarts after it is not used for a long time.
The dust inside the unit is blown out again.
When the unit is running.
The odors absorbed in are blown out again.
3 Error description If some error occurs when the unit is running, the error code will be displayed on the wired controller and the main board
of the outdoor unit.See the table before for more details about the meaning of each error error.. Table 15 Indicating Lamp
Residential AC Errors
Commerical AC Errors
Outdoor Unit "88"
/ Short/open circuit of the liquid valve temperature sensor
Defrosting mode 1 Defrosting mode 2 heating overload protection Normal running running Short/open circuit of he liquid valve temperature sensor
Short/open circuit of the gas valve temperature sensor
Short/open circuit of the gas valve temperature sensor
/ /
Wired Controller Display
Running
Cooling
Heating
08
/
/
/
/
/
0A
/
/
/
/
/
Flash 3 times /
Flash 3 times /
Flash 3 times /
/
oE
/
/
Shown as Table 16
/
Flash 19 times
/
b5
b5
Shown as Table 16
/
Flash 22 times
/
b7
b7
Display /
Lamp Panel "88" Display (Floor Ceiling Type)
0C ON
15
Troubleshooting Refrigerant insufciency or blockage protection (available for the residential outdoor unit)
Refrigerant insufciency or blockage protection (available for the residential outdoor unit)
Short/open circuit of the indoor ambient
Short/open circuit of the indoor ambient
temperature sensor Short/open circuit of the indoor evaporator Short/open circuit of the of the outdoor ambient temperature sensor
temperature sensor Short/open circuit of the indoor evaporator Short/open circuit of the of the outdoor ambient temperature sensor
Short/open circuit of the
Short/open circuit of the
temperature sensor at the midway of the condenser coil ( for the commercial unit) Short/open circuit of the outdoor discharge temperature sensor Oil returning in cooling System high pressure protection
temperature sensor at the midway of the condenser coil ( for the commercial unit) Short/open circuit of the outdoor discharge temperature sensor Oil returning in cooling System high pressure protection
Anti-freezing protection System low pressure protection (reserved) Compressor discharge high temperature protection Whole unit over-current
Compressor discharge high temperature protection Whole unit over-current
protection Communication error between the indoor and outdoor units
protection Communication error between the indoor and outdoor units
F0
/
Shown as Table
/
16
Flash 10 times
Flash
/
oE
oE
/
F1
F1
once
Shown as Table 16
/
Flash twice
/
F2
F2
F3
/
Flash 3 times
/
F3
F3
F4
/
Flash 4 times
/
F4
F4
F5
/
Flash 5 times
/
F5
F5
F7
/
/
/
/
/
E1
Flash once
/
/
E1
E1
Anti-freezing protection
E2
Flash twice
/
/
E2
E2
System low pressure protection
E3
Flash 3 times
/
/
E3
E3
E4
Flash 4 times
/
/
E4
E4
E5
Flash 3 times
Flash 3 times
Flash 3 times
oE
oE
Shown as Table 16
Flash 6 times
/
/
E6
E6
16
Troubleshooting Mode conict
Mode conict
Shown as Table 16
Overload protection
Overload protection
E8
Anti cold blow protection
/
/
Indoor unit water overow error
Trial run/trial operation
Trial run/trial operation
Refrigerant recovery mode Drive module resetting(for the commercial unit) Min. cooling/ heating (capability test code)
Refrigerant recovery mode
Fo
Quick ash
Quick ash
/
Fo
Fo
IPM Drive module resetting
P0
Flash 3 times
Flash 3 times
Flash 3 times
oE
oE
/
Quick ash
/
P0
/
/
Quick ash
P0
/
Quick ash
/
P3
/
/
Quick ash
P3
P5
Flash 3 times
Flash 3 times
Flash 3 times
oE
oE
P6
Flash 3 times
Flash 3 times
Flash 3 times
oE
oE
P7
Flash 3 times
Flash 3 times
Flash 3 times
oE
oE
Flash 3
Flash 3
Flash 3
oE
oE
times
times
times
Mid. Cooling/ heating (capability test code) Phase overcurrent protection
Cooling IPLV test Cooling IPLV test Cooling level leve l AA performance test Level AA cooling performance test Compressor over-current protection
Flash 7 times
/
/
E7
E7
Flash 3 times
Flash 3 times
Flash 3 times
oE
oE
/
/
/
/
/
/
Flash
Flash
E9
E9
Quick ash
Quick ash
Quick ash
dd
dd
E9
dd
P0
P3
P0
P3
Short/open circuit of the of the module temperature sensor
Communication error between the inverter driver to the main controller Short/open circuit of the of the module temperature sensor
Module temperature protection
Module temperature protection
P8
AC contact protection
P9
Flash 3 times
Flash 3 times
Flash 3 times
oE
oE
Circuit sensor error
Pc
Flash 3 times
Flash 3 times
Flash 3 times
oE
oE
Transducer connection protection
Pd
Flash 3 times
Flash 3 times
Flash 3 times
oE
oE
AC current protection(input protection(input side)
PA
Flash 3 times
Flash 3 times
Flash 3 times
oE
oE
Temperature drift protection
PE
Flash 3 times
Flash 3 times
Flash 3 times
oE
oE
Drive board communication error(for the commercial unit)
AC contact protection (for (for the commercial unit) Circuit sensor error Transducer connection protection (for (for the commercial unit) AC current protection(input protection(in put side) Temperature drift protection (for the commercial unit)
17
Troubleshooting Drive board ambient temperature sensor error (for the commercial unit)
Too high power protection (available for the residential outdoor unit)
Too high power protection (available for the residential outdoor unit)
L9
Flash 20 times
/
/
oE
oE
Compressor startup failure
Compressor startup failure
Lc
Flash 3 times
Flash 3 times
Flash 3 times
oE
oE
Compressor phase failure/ reverse protection
Compressor phase failure/ reverse protection
Ld
Flash 3 times
Flash 3 times
Flash 3 times
oE
oE
Compressor rotation failure(for the
Compressor rotation failure(for the
LE
Flash 3 times
Flash 3 times
Flash 3 times
oE
oE
commercial unit)
commercial unit)
Over speed (for the commercial unit)
Over speed
LF
Flash 3 times
Flash 3 times
Flash 3 times
oE
oE
18
Troubleshooting Short/open circuit of the temperature sensor at the inlet of the condenser coil ( for the commercial unit)
/
A5
/
/
/
/
/
/
A7
/
/
/
/
/
Memory card error
/
EE
/
/
/
/
/
Frequency limitation/ degradation for module circuit protection (for (for phase circuit)
/
En
/
/
/
/
/
/
EU
/
/
/
/
/
/
F6
/
Flash 6 times
/
/
/
/
F8
/
Flash 8 times
/
/
/
/
F9
/
Flash 9 times
/
/
/
/
FH
/
Flash 2 times
Flash 2 times
/
/
/
H6
Flash 11 times
/
/
/
/
Compressor demagnetizing protection
/
HE
/
/
/
/
Indoor and outdoor units unmatched
/
/
/
Short/open circuit of the temperature sensor at the outlet of the condenser coil ( for the commercial unit)
Frequency limitation/ degradation for module temperature protection Frequency limitation/ degradation for overload Frequency limitation / degradation for circuit protection of the whole unit Frequency limitation/ degradation for module circuit protection (for (for phase circuit) Frequency limitation/ degradation for anti-freezing protection No indoor fan motor
Flash 14 times
LP
Flash 19 times
19
/
/
Troubleshooting Compressor phase circuit detection error DC link voltage drop error Zero detection circuit error Nominal cooling/heating (capability test code) Max. cooling/ heating (capability test code)
/
U1
/
/
Flash 12 times
/
/
/
U3
/
/
Flash 20 times
/
/
/
U8
Flash 17 times
/
/
/
/
/
P1
/
/
/
/
/
/
P2
/
/
/
/
/
The words in gray means the corresponding function is unavailable. Table 16 Error Code
Error Description
Error Code
Error Description
Error Code
Error Description
13
Unit A indoor unit pipe outlet temperature sensor error
23
Unit B indoor unit pipe outlet temperature sensor error
33
Unit C indoor unit pipe outlet temperature sensor error
14
Unit A indoor pipe inlet temperature sensor error
24
Unit B indoor pipe inlet temperature sensor error
34
Unit C indoor pipe inlet temperature sensor error
15
Unit A indoor ambient temperature sensor error
25
Unit B indoor ambient temperature sensor error
35
Unit C indoor ambient temperature sensor error
16
Unit A mode conict
26
Unit B mode conict
36
Unit C mode conict
17
Unit A antifreezing protection
27
Unit B antifreezing protection
37
Unit C antifreezing protection
41
Unit D communication error
54
Unit E indoor pipe inlet temperature sensor error
42
Unit D indoor pipe midway temperature sensor error
43
Unit D indoor unit pipe outlet temperature sensor error
44
Unit D indoor pipe inlet temperature sensor error
45
Unit D indoor ambient temperature sensor error
Unit D mode
46
conict
47
Unit D antifreezing protection
55
Unit E indoor ambient temperature sensor error
51
Unit E communication error
56
Unit E mode conict
52
Unit E indoor pipe midway temperature sensor error
57
Unit E antifreezing protection
53
Unit E indoor unit pipe outlet temperature sensor error
C5
Jumper terminal error
20
Troubleshooting Table 17 Error description of outdoor refrigerant pipe detection function Wiring error or component error
Unit which is detecting
Unit which isn’t detecting
5E
01
**
5E
02
**
5E
03
**
5E
04
**
5E
05
**
Indoor unit gas pipe connection error or component error
Unit which is detecting
--
5P
01
--
5P
02
--
5P
03
--
5P
04
--
5P
05
--
Fig.12 Outdoor Unit: AM5O-120HPDC1 (Note: Refer to the real products for the exact position of each component.) Once errors are displayed on the controller, please shut off the air conditioning unit and contact the professionally skilled personnel for troubleshooting.
4 After-Sales Service If there is any quality or other issue, place contact the GREE after-sales service center.
21
Function Description
Ⅶ Function Description Refrigerant Recovery
The refrigerant can be recovered from either the indoor unit or the outdoor unit. From the outdoor unit: it is available to recover the refrigerant from the outdoor unit by pressing “SW3”for a long time period. From the indoor unit: when the unit is powered on and runs under the COOL mode, it is available within ve minute to go the refrigerant recovery mode by pressing three times the “LIGHT” button on the wireless controller in three seconds with “F0”displayed. How to quit the refrigerant recovery: When the refrigerant recovery has started, it will quit when the “SW3” is pressed down for a long time period or there is a signal from the wireless controller or it has run for ten minutes. Forcible Defrosting
How to activate this function: when indoor unit runs under the heating mode and at 16℃ , it will activate the forcible defrosting by pressing the “+”and “-” buttons alternately three times in ve seconds. How to quit this function: the function will quit when the mode of indoor units conicts. Switchover of the Defrosting Modes
Under the unit is under the “Off” status, if “H1” is not displayed on the wireless controller, then the unit will go to the defrosting mode 1 when it is turned on through the wireless controller. Under the unit is under the “Off” status, if “H1” is displayed on the wireless controller, the unit will go the defrosting mode 2 when it is turned on through the wireless controller. Under the unit is under the “Off” status, it is available to switch over the defrosting mode 1 and defrosting mode 2 by pressing the “Mode” and “Blow” buttons simultaneously.
22
Performance Parameters
Ⅷ Performance Parameters Rated Working Working Conditions of the Air Conditioning Unit Table 18 Working Tempera Temperature ture Range Indoor side state
Outdoor side stae
Dry bulb temp. ℃
Wet bulb temp. ℃
Dry bulb temp. ℃
Wet bulb temp. ℃
Rated Cooling
27
19
35
24
Max. cooling
32
23
48
26
Min. cooling
21
15
18
—
Rated Heating
20
15
7
6
Max. heating
27
—
24
18
Min. heating
20
15
- 15
- 16
Notes: ① . The heating/cooling capacity and noise listed below are all measured before the shipment. ② . All parameters listed below are measured under the standard working conditions. If there is any
change, the parameters marked on the nameplate always prevail. ③ . The heating capacity of the indoor unit just involves that of the heat pump but apart from that of the