Danfoss BD Compressors
Direct current & multivoltage applications 12-24 V DC • 100-240 V AC, 50/60 Hz
REFRIGERATION & AIR CONDITIONING DIVISION
Collection of datasheets
Shock absorber Stator Current lead-in
Permanent magnet
Shock absorber
1
DEHC.PK.100.C9.02/520N0916
8175-2
November 2009
Contents
General / Data stamping Label design / VDE-UL approvals Warnings / Connectors / Mounting accessories / Filter drier selection Electric circuit / Electronic units & wiring / Voltage range Electronic unit 101N0230 / Mounting the electronic unit Cable dimensions / Compressor speed
Page 3 4 5 6 7 7
Thermostat connection / Fan connection / Lamp connection / LED connection 8 Troubleshooting / Protection systems Images: BD35F compressor with electronic unit 101N0500 / Electronic units 9 10
BD35F BD35F (inch)
Technical data Performance data Technical data (inch connectors) Performance data (inch connectors)
11 12 13 14
BD50F BD50F (inch)
Technical data Performance data Technical data (with inch connectors) Performance data (with inch connectors)
15 16 17 18
BD80F
Technical data Performance data
19 20
BD250GH
Technical data Performance data
21 22
BD250/250GH Technical data (Twin Compressor) Performance data
23 24
BD35K Technical data (Solar Applications) Performance data
25 26
BD100CN
Technical data Performance data
27 28
Remote kit for BD compressors AC line cord for BD electronic unit 101N0500 BD code numbers / Accessories
29 29 30
November 2009
DEHC.PK.100.C9.02/520N0916
2
General
Danfoss variable speed refrigeration compressors type BD35F, BD50F, BD80F and BD250GH are designed for connection to 12V and 24V DC power supply and for refrigerant R134a (CF3-CH2F). The compressors are intended especially for use in mobile applications, e.g. cooling boxes, boats, caravans, trucks, vans and buses. Due to their low energy consumption and the option for a wide supply voltage range, the compressors are also very suitable for stationary applications powered by photovoltaic solar panels. The compressors can be used in refrigerators and freezers using either capillary tube or TEV as the throttling device. The compressors BD35K and BD100CN are especially designed for refrigeration systems using isobutane, refrigerant R600a (C4H10) and propane, refrigerant R290 (C3H8), respectively, as can be seen from the individual type label information. R600a and R290 are classified as flammable refrigerants of class A3 according to ANSI/ASHRAE 34. Accordingly, special safety regulations must be complied with. A special Test Schedule has been integrated in the European Standards EN 60335-2-24 for domestic and EN 60335-2-89 for commercial appliances and in the corresponding international standards IEC 60335-2-24 and IEC 60335-2-89. The compressors BD35K and BD100CN must only and exclusively be used in appliances certified for flammable refrigerants according to these or later regulations. This means that the compressors must not be used in appliances which are not originally designed and certified for flammable refrigerants. These compressors are designed for stationary use only. The BD compressor concept includes an electronic unit which features overload protection, battery protection; fan, LED, lamp connections; load dump and Adapative Energy Optimizing. The electronic unit has internal voltage recording and calibration to the applied voltage. The electronic unit may also be powered directly from certain types of electronic power supply units and thus no battery is required. In addition to being especially quiet in operation - approx. 35db(A) at 3000 rpm, the compressors have a high COP value and they will operate under continual heeling of 30° such as occurs on boats. The BD compressors must be mounted in a dry and clean place. The compressors will withstand storage temperatures down to -35°C. Condensing temperatures: Max. 60°C at stable conditions and max. 70°C at peak load. Ambient temperatures: Min. -10°C, max. 55°C
Acoustic noise & tilt angle
Data stamping
Danfoss Compressors have a manufacturing date code stamping on the front of the housing. The content of the coding is 2 lines, with 6 and 7 characters each, according to the example below. Z02007 (6 characters) 119A01F (7 characters) Composition of line 1 Z0200: Compressor type information (101Z0200 = Z0200) 7: internal Danfoss code Composition of line 2 11: Production week 9: Production year A: Production day A = Monday, B = Tuesday, C = Wednesday, D=Thursday, etc. 01: Production hour 00 to 23 or shift code -1, -2, -3 F: Danfoss Compressors internal production location code A to G, U Germany A until week 50/2005 D until week 35/2006 K to N Slovenia A, D, R Slovakia A from week 01/2006 D from week 38/2006 R from week 01/2005 S, R Mexico R up to week 27/2004 W China In addition the production location code will in the future be marked - for export reasons (outside EU) - with the country of origin on the type label. Example for the barcode on the printed circuit board (inside the electronic unit): 0727200983 (10 characters) 072: Production day 7: Production year 2: Number of lot 00983: Number of electronic unit
3
DEHC.PK.100.C9.02/520N0916
November 2009
Label design
Electronic unit label Voltage
For the electronic unit, the code for date of manufacture is located on a label on the backside of the housing. All BD compressors are designed to meet specifications according to the EC type-approval certificate. In addition we have VDE and UL approval on most products (see table below for further information).
UL label
BD type label
RoHS marking
Nominal voltage has been removed from the BD type label and moved to the electronic unit. LBP/MBP marking has also been removed. VDE marking will not appear on the BD type label due to the fact that the compressor can be applied with non VDE approved electronic units. The label on the electronic unit contains the nominal supply voltage. Located between + and – terminal. The AC/DC electronic contains in addition the applied nominal AC voltage.
VDE/UL approvals Approved compressor electronic unit combinations
Compressors Standard 101N0210 BD35F mm BD35F inch BD35K (R600a) BD50F mm BD50F inch BD80F mm BD250GH BD250GH Twin BD100CN (R290) Compressors AC/DC conv. 101N0500 BD35F mm BD35F inch BD35K (R600a) BD50F mm BD50F inch BD80F mm BD250GH BD250GH Twin BD100CN (R290) 101Z0200 101Z0204 101Z0211 101Z1220 101Z0203 101Z0280 101Z0400 101Z0500 101Z0401
VDE/UL VDE/UL UL UL VDE/UL VDE/UL
Electronic Units High start 101N0230 High speed 101N0290 Automotive Automotive 101N0600 101N0630
VDE/UL
= Combination possible, VDE or UL approval = Combination possible, but no approval = Combination not possible
November 2009
DEHC.PK.100.C9.02/520N0916
4
Warnings (BD35K, BD100CN)
R600a is flammable in concentrations of air between approximately 1.5% and 8.5% by volume (LEL lower explosion limit and UEL upper explosion limit). An ignition source at a temperature higher than 460°C is needed for a combustion to occur. Isobutane is significantly different from R12 and R134a. This means that compressors for R600a cannot be used with R12 or R134a.
R290 is flammable in concentrations of air between approximately 2.1% and 9.5% by volume (LEL lower explosion limit and UEL upper explosion limit). An ignition source at a temperature higher than 470°C is needed for a combustion to occur.
No high potential test nor start tests must be carried out while the compressor is under vacuum. No attempt must be made to start the compressor without a complete starting device. Allow the compressor to reach a temperature above 10°C before starting the first time in order to avoid starting problems. Anti-freeze agents must not be used in the compressors as such agents are damaging to several of the materials used. In particular, the ethyl or methyl alcohol contents of such anti-freeze agents have a destructive effect on the synthetic motor insulation. Connectors The compressor is equipped with DANCON connectors which consist of a thick-walled, copper plated steel tube with high corrosion resistance, and a solderability equal to that of conventional copper connectors. DANCON connectors are equipped with an aluminium cap (Capsolut) which gives a tight sealing. The seal cap is easily removed with an ordinary pair of pliers or with a special tool. (code number 118X2030)
Mounting accessories
Washer Compressor base
Nut M6 Grommet sleeve
8185
Washer Compressor base
Clip Steel pin
9
3327-2
7382-2
Cabinet base
Screw M6 x 25
Rubber grommet
Cabinet base
Rubber grommet
Bolt joint
Snap-on joint
The mounting accessories for the compressors are available in two versions, with bolt joint or snap-on joint. The rubber grommets are designed for the 16 mm holes of the baseplate. Bolt joint for one compressor in a bag 118-1917 Bolt joint in quantities 118-1918 Snap-on in quantities 118-1919
Filter drier selection
Only filter driers which are declared by the manufacturer to be suitable for mobile applications must be used in refrigeration systems with BD compressors. Filter material powder ending up in the compressor will lead to excessive wear of the piston and transmission parts, and metal particles deposited in the motor windings will cause the compressor to stop because the electric signal back to the electronic unit is disturbed.
5
DEHC.PK.100.C9.02/520N0916
November 2009
9
Electric circuit
The BD compressors are fitted with a brushless direct current motor which is electronically commutated by an electronic unit. The electronic unit is delivered separately and must be mounted on the compressor, please see instructions page 7. The electronic unit must always be connected directly to the battery poles or power supply unit terminals. For the protection of the installation an external fuse must be installed in the power supply cable close to the battery or power supply unit. If the chassis is used as a conductor, a proper connection between cable and chassis must be established. Wrong polarity applied to the electronic unit does not destroy the unit, however, the compressor does not work. If the compressor is planned to be stopped for a longer period, a main switch can be installed to avoid the battery from being drained.
Electronic units & wiring
available units: BD35F: 101N0210, 101N0220, 101N0300, 101N0320, 101N0400, 101N0500, 101N0600, 101N0630 BD50F: 101N0210, 101N0220, 101N0230, 101N0300, 101N0320, 101N0500 BD80F: 101N0290 BD250GH: 101N0290, BD250/250GH: 2 x 101N0290 BD35K: 101N0400, 101N0210, 101N0220 BD100CN: 101N0290 Voltage range BD35/50/80F/250GH/100CN: 12V DC systems: 10.4V cut-out (or 9.6V with optional setting) - 17V max. ; 24V DC systems: 22.8V cut-out (or 21.3V with optional setting) - 31.5V max. The low voltage limits can be established if a connection is made between the terminals C and P, please see also the passage Optional battery protection settings page 9. The electronic unit will calibrate to the applied voltage. This means that if the battery voltage is less than 17V, the electronic unit assumes that it is working in a 12V system. If the voltage is higher than 17V, the electronic unit assumes that it is working in a 24V system. Consequently, the compressor does not run at power supply voltages between about 17V and the desired battery protection cut-out voltage for 24V systems. A continuous voltage range from 9.6V to 31.5V can be established if a 220kΩ resistor (wiring diagram item 9) is connected between the terminals C and P. This wide voltage range makes the BD compressors very suitable for photovoltaic powering. BD35F/BD35K: Solar systems (electronic unit 101N0400): 10V - 45V, no battery protection BD35/50F: AC power supply systems: Nominal voltages from 100 to 240V AC, 50/60Hz. 85V min. - 265V max., 50/60Hz. Power consumption is limited to 100W with the BD50F compressors. Earth connection required. All voltages are measured on the terminals of the electronic units.
DEHC.PK.100.C9.02/520N0916 6
November 2009
Electronic unit 101N0230
In applications providing pressure equalization before compressor start and operating in ambient conditions below 32oC (90oF), electronic unit 101N0210 is appropriate for both the BD35F and BD50F compressors. Electronic unit 101N0230 is offered for use with Danfoss BD50F compressors to provide additional starting torque for the BD50F compressor. Electronic unit 101N0230 is not suitable for use with the BD35F compressor. The BD50F has a stronger motor than the BD35F and can tolerate the higher start current furnished by the 101N0230 electronic unit. The cable plug of the electronic unit is mounted on the pins of the current lead-in on the compressor. Then the electronic unit itself is mounted on the bracket of the compressor. At first the left side is mounted, then the right side is pressed over the screw on the bracket. The electronic unit snaps on to the bracket and is now securely mounted on the compressor. In case the electronic unit must be removed from the compressor, the screw has to be dismantled. Earth connection (via compressor baseplate) can be used if required.
Mounting the electronic unit
8194-2
Cable dimensions
To ensure correct start and operating conditions, the following cable dimensions must be observed:
BD35/50F & BD35K:
Size Cross AWG section Max. length* 12V operation Max. length* 24V operation
BD35/50F AC operation: Cross section min. 0.75 mm2 or AWG 18
[mm2] [Gauge]
[m]
[ft.]
[m]
[ft.]
8
8
2.5
8
5
16
*Length between battery an electronic unit
Compressor speed
Without any resistor in the control circuit, the compressor will run with a fixed speed of 2,000/2,500 rpm when the thermostat is switched on, depending on the electronic unit version (see tables below). Other fixed speeds in the range between 2,000/2,500 and 3,000/3,100/3,800 or 3,500/4,400rpm can be obtained when a resistor (R1) is installed between terminal C and P to adjust the current of the contol circuit (please see wiring diagrammes page 6). In AEO (Adaptive Energy Optimizing) speed mode the BD compressor will always adapt its speed to the actual cooling demand within a random operation voltage of 9.6 to 31.5V. In solar applications without a battery a 220 kΩ resistor is recommended.
Compressor Electronit unit Code number 101N0210 101N0220 101N0500 101N0600/0630 101N0300 101N0320 101N0400 with AEO 101N0210 101N0220 101N0230 101N0500 101N0300 101N0320 with AEO Resistor (R1) [Ω]
calculated values
BD compressors can operate with normal mechanical type thermostats as used in refrigeration appliances, or with electronic thermostats. The thermostat is connected between the terminals C and T of the electronic unit. The compressor current does not flow through the thermostat contacts. When the thermostat is cut out there will still be power to the electronic unit. A system with no stand-by power consumption can be established if the thermostat is replaced by a jumper between the terminals C and T, and the main switch is replaced by a thermostat. In this case battery protection does not work and supply voltage needs to be bigger than cut-in voltage. The full compressor current flows through the thermostat, which must be rated accordingly.
Fan connection
If a fan is to be used, it must be connected to the electronic unit terminals + and F. On electronic unit 101N0600 and 101N00630 a fan must be connected to C andF. Always use a 12V fan, also in 24V systems, as the electronic unit will automatically reduce the applied voltage to 12V for the fan. Using the special solar electronic unit 101N0400, the fan runs with input voltage always. The max. load on the electronic unit is 0.5Aaverage or 1Apeak . The fan is allowed to start with a higher current for the first 2 seconds. If the fan becomes overloaded, both fan and compressor will be cut out by the overload protection.
Lamp connection
A 12V DC 5 Watt lamp can be connected between the terminals A and C on electronic unit 101N0500, 101N0600 and 101N0630. The output voltage between the terminals A and C is always regulated to 12V DC. A 12V DC lamp must be used for both 12V and 24V power supply systems. The lamp output can supply a continuous current of 0.5Aaverage
LED connection
A 10mA Light Emitting Diode (LED) for compressor operation monitoring can be connected between the terminals + and D. Operational errors will cause the LED to flash a number of times. The number of flashes depends on what kind of operational error was recorded. Each flash will last ¼ second. After the actual number of flashes there will be a delay with no flashes, so that the sequence for each error recording is repeated every 4 seconds. Operational errors shown by LED (optional):
BD35/50F, BD35K
Number of flashes Error type
BD80F, BD100CN, BD250GH, BD250/250GH
Number of flashes Error type
5
Thermal cut-out of electronic unit
(If the refrigeration system has been too hea vi ly loaded, or if the ambient tem pe ra ture is high, the electronic unit will run too hot).
5
Thermal cut-out of electronic unit
(If the refrigeration system has been too hea vi ly loaded, or if the ambient tem pe ra ture is high, the electronic unit will run too hot).
4
Minimum motor speed error
(If the refrigeration system is too heavily loaded, the motor cannot maintain minimum speed at approximately 1,850 rpm).
4
Minimum motor speed error
(If the refrigeration system is too heavily loaded, the motor cannot maintain minimum speed at approximately 2,450 rpm).
3
Motor start error
(The rotor is blocked or the differential pressure in the refrigeration system is too high (>5 bar)).
3
Motor start error
(The rotor is blocked or the differential pressure in the refrigeration system is too high (>5 bar)).
2
Fan over-current cut-out
(The fan loads the electronic unit with more than 1Apeak).
2
Fan over-current cut-out
(The fan loads the electronic unit with more than 1Apeak).
1
Battery protection cut-out
(The voltage is outside the cut-out setting).
1
Battery protection cut-out
(The voltage is outside the cut-out setting).
November 2009
DEHC.PK.100.C9.02/520N0916
8
Troubleshooting
To diagnose why a compressor comes to an unintended stop, it is recommended to have a 10mA Light Emitting Diode (LED) installed between the terminals + and D, please see page 3 and 4. Provided that the electronic unit is properly connected to the power supply, and the thermostat is on, the number of flashes emitted by the LED will give a hint about the reason for the interruption of the compressor operation. The motor windings can be checked for defects by measuring the resistance between the current leadin pins. If the measured values between all 3 pins are approximately the same, the motor is most likely all right. The electronic unit is not to be repaired, it should not be opened at all. The BD compressor protection system facilitates protection against compressor overload and start failure, fan overload and electronic unit overheating as well as destructive battery discharge. When overload protection is activated, the compressor enters a cycle in which it attempts to start at approximately 66 seconds intervals until a successful start is achieved. The compressor overload and start protection cuts off power to the compressor if the compressor speed drops below approximately 1,850 rpm (BD35F/BD50F/BD35K) or 2,450 rpm (BD80F/BD250GH/BD100CN) or if this motor speed is not reached during the start sequence. Possible reasons for overload protection activating could be excess refrigeration system pressures during operation or an excessive pressure differential. The fan overload protection stops the compressor and fan if the fan current exceeds 0.5Aaverage or 1Apeak . If the electronic unit heat sink senses a temperature >100°C it will cause the compressor to stop. Restart will occur automatically when the temperature has dropped. (<90°C, with 66 seconds additional delay). If a fan is installed, it will continue to run if the compressor stops due to overload or electronic unit overheating. If a voltage outside the specified range is applied to the electronic unit, the compressor does not start, or it stops if the voltage limit is exceeded during operation. The compressor will restart automatically approximately 60 seconds after the supply voltage has reached the reset voltage within the range in question. If a fan is installed, it will start to operate without a delay as soon as the reset voltage is reached. To ensure sufficient battery power for correct compressor operation or to avoid permanent damage to the battery because of heavy discharge, the BD electronic unit has integrated battery protection (except electronic unit 101N0400). The compressor is stopped and restarted again according to the dedicated voltage limits measured on the + and - terminals of the electronic unit. Other battery protection settings are optional if a connection, which includes a resistor, is established between terminals C and P, please see the wiring diagrammes page 6. Standard battery protection settings (no connection C - P)
12V cut-out [V] 10.4 12V cut-in [V] 11.7 24V cut-out [V] 22.8 24V cut-in [V] 24.2
Electronic Units
November 2009 DEHC.PK.100.C9.02/520N0916 10
BD35F Direct Current Compressor R134a, 12-24V DC , 10-45V DC Solar & 100-240V AC 50/60Hz
General Code number (without electronic units) Electronic unit 12-24V DC - standard Electronic unit 12-24V DC - with metal shielding Electronic unit 12-24V DC - with AEO Electronic unit 12-24V DC - with AEO & metal shielding Electronic unit 10-45V - for solar applications Electronic unit 12-24V DC & 100-240V AC 50/60Hz Electronic unit 12-24V DC - for automotive applications Electronic unit 12-24V DC - for automotive applications Approved compressor - electronic unit combinations Additional approvals Compressors on pallet Application Application Evaporating temperature Voltage range (DC & AC) Max. condensing temperature continuous (short) Max. winding temperature continuous (short) 101Z0200 single: 101N0210, 30 pcs: 101N0211 single: 101N0220, 30 pcs: 101N0221 single: 101N0300, 30 pcs: 101N0301 single: 101N0320, 30 pcs: 101N0321 single: 101N0400, 30 pcs: 101N0401 single: 101N0500, 36 pcs: 101N0501 single: 101N0600, 30 pcs: 101N0601 single: 101N0630, 30 pcs: 101N0631 refer to Technical Info DEHC.EI.100.C e4, C-Tick 150
LBP/MBP/HBP -30 to 0 (10) 12-24V DC & 100-240V AC 50/60Hz 10-45V DC for solar applications °C 60 (70) °C 125 (135) °C HBP S S S
Cooling requirements Application LBP MBP 32°C S S 38°C S S 43°C S S Remarks on application: Fan cooling F1 depending on application and speed. Motor Motor type Resistance, all 3 windings (25°C) Design Displacement Oil quantity (type) Maximum refrigerant charge Free gas volume in compressor Weight - Compressor/Electronic unit Dimensions Height Variable speed 2.2 2.00 150 (polyolester) 300 870 4.3/0.25
S = Static cooling normally sufficient O = Oil cooling F1 = Fan cooling 1.5 m/s (compressor compartment temperature equal to ambient temperature) F2 = Fan cooling 3.0 m/s necessary SG = Suction gas cooling normally sufficent – = not applicable in this area
Ω cm3 cm3 g cm3 kg
204 170
Suction connector Process connector Discharge connector Connector tolerance
mm A 137 B 135 B1 128 B2 73 location/I.D. mm | angle C 6.2 | 41.5° location/I.D. mm | angle D 6.2 | 45° location/I.D. mm | angle E 5.0 | 21° I.D. mm ±0.09, on 5.0 +0.12/+0.20 24V cut-in [V] 24.2
78.5
ø16
D
ø4.2
127
C
Standard battery protection settings (no connection C - P) 12V cut-out [V] 12V cut-in [V] 24V cut-out [V] 10.4 11.7 22.8
Operational errors shown by LED (optional)
Number of flashes Error type
5
Thermal cut-out of electronic unit
(If the refrigeration system has been too hea vi ly loaded, or if the ambient tem pe ra ture is high, the electronic unit will run too hot).
In AEO (Adaptive Energy Optimizing) speed mode the BD compressor will always adapt its speed to the actual cooling demand.
Datasheet: DEHC.ED.100.D6.02 / November 2009
Accessories for BD35F Bolt joint for one compressor Ø: 16 mm Bolt joint in quantities Ø: 16 mm Snap-on in quantities Ø: 16 mm Remote kit (without cable) AC line cord (UL approved/VDE approved) DC usage: Std. automobile fuse12V: 15A / 24V: 7.5A Main switch: rated to min. 20A AC usage: Fuse 100-240V: 4A / Main switch: min. 6A
Not deliverable from Danfoss
November 2009
DEHC.PK.100.C9.02/520N0916
12
BD35F Direct Current Compressor (Inch Connectors), R134a, 12-24V DC, 10-45V DC Solar & 100-240V AC 50/60Hz
Compressors Code number (without electronic units) Electronic unit 12-24V DC - standard Electronic unit 12-24V DC - with metal shielding Electronic unit 12-24V DC - with AEO Electronic unit 12-24V DC - with AEO & metal shielding Electronic unit 10-45V - for solar applications Electronic unit 12-24V DC & 100-240V AC 50/60Hz Electronic unit 12-24V - for automotive applications Electronic unit 12-24V - for automotive applications Approved compressor - electronic unit combinations Additional approvals Compressors on pallet Application Application Evaporating temperature Voltage range (DC & AC) Max. condensing temperature continuous (short) Max. winding temperature continuous (short) 101Z0204 single: 101N0210, 30 pcs: 101N0211 single: 101N0220, 30 pcs: 101N0221 single: 101N0300, 30 pcs: 101N0301 single: 101N0320, 30 pcs: 101N0321 single: 101N0400, 30 pcs: 101N0401 single: 101N0500, 36 pcs: 101N0501 single: 101N0600, 30 pcs: 101N0601 single: 101N0630, 30 pcs: 101N0631 refer to Technical Info DEHC.EI.100.C e4, C-Tick 150 LBP/MBP/HBP -20 to 50 12-24V DC & 100-240V AC 50/60Hz 10-45V DC for solar applications °F 140 (158) °F 257 (275) °F HBP S S S
Cooling requirements Application LBP MBP 32°C S S 38°C S S 43°C S S Remarks on application: Fan cooling F1 depending on application and speed. Motor Motor type Resistance, all 3 windings (25°C) Design Displacement Oil quantity (type) Maximum refrigerant charge Free gas volume in compressor Weight - Compressor/Electronic unit Dimensions Height Variable speed 2.2 0.12 5.1 (polyolester) 10.5 29.6 9.5/0.55 5.39 5.32 5.04 2.87 0.252-0259 | 41.5° 0.252-0259 | 45° 0.202-0.205 | 21°
S = Static cooling normally sufficient O = Oil cooling F1 = Fan cooling 1.5 m/s (compressor compartment temperature equal to ambient temperature) F2 = Fan cooling 3.0 m/s necessary SG = Suction gas cooling normally sufficent – = not applicable in this area
Ω cu.in. fl.oz. oz. fl.oz. lbs.
0.63"(16)
Suction connector Process connector Discharge connector
inch A B B1 B2 location/I.D. in. | angle C location/I.D. in. | angle D location/I.D. in | angle E
4.13"(105)
1.81" (46)
1.10" (28)
4.84"(123)
Standard battery protection settings (no connection C - P) 12V cut-out [V] 12V cut-in [V] 24V cut-out [V] 10.4 11.7 22.8
Operational errors shown by LED (optional)
Number of flashes Error type
5
Thermal cut-out of electronic unit
(If the refrigeration system has been too hea vi ly loaded, or if the ambient tem pe ra ture is high, the electronic unit will run too hot).
Test conditions Condensing temperature Ambient temperature Suction gas temperature Liquid temperature
ASHRAE 130°F 90°F 90°F 90°F
EN 12900/CECOMAF 131°F 90°F 90°F no subcooling Code number 118-1917 118-1918 118-1919 105N9210 105N9520/30 Not deliverable from Danfoss
In AEO (Adaptive Energy Optimizing) speed mode the BD compressor will always adapt its speed to the actual cooling demand.
Accessories for BD35F Bolt joint for one compressor Ø: 5/8 in. Bolt joint in quantities Ø: 5/8 in. Snap-on in quantities Ø: 5/8 in. Remote kit (without cable) AC line cord (UL approved/VDE approved) DC usage: Std. automobile fuse12V: 15A / 24V: 7.5A Main switch: rated to min. 20A AC usage: Fuse 100-240V: 4A / Main switch: min. 6A
Datasheet: DEHC.ED.100.L6.22 / November 2009
November 2009
DEHC.PK.100.C9.02/520N0916
14
BD50F Direct Current Compressor, R134a 12-24V DC & 100-240V AC, 50/60Hz
General Code number (without electronic units) Electronic unit 12-24V DC - standard Electronic unit 12-24V DC - with metal shielding Electronic unit 12-24V DC - high start performance Electronic unit 12-24V DC - with AEO Electronic unit 12-24V DC - with AEO & metal shielding Electronic unit 12-24V DC & 100-240V AC 50/60Hz Approved compressor - electronic unit combinations Additional approvals Compressors on pallet Application Application Evaporating temperature Voltage range (DC & AC) Max. condensing temperature continuous (short) Max. winding temperature continuous (short) 101Z1220 single: 101N0210, 30 pcs: 101N0211 single: 101N0220, 30 pcs: 101N0221 single: 101N0230, 30 pcs: 101N0231 single: 101N0300, 30 pcs: 101N0301 single: 101N0320, 30 pcs: 101N0321 single: 101N0500, 36 pcs: 101N0501 refer to Technical Info DEHC.EI.100.C e4, C-Tick 150 LBP/MBP/HBP -30 to 0 (10) 12-24V DC & 100-240V AC 50/60Hz °C 60 (70) °C 125 (135) °C HBP F1 F1 F1
Cooling requirements Application LBP MBP 32°C S S 38°C S S 43°C S S Remarks on application: Fan cooling F1 depending on application and speed. Motor Motor type Resistance, all 3 windings (25°C) Design Displacement Oil quantity (type) Maximum refrigerant charge Free gas volume in compressor Weight - Compressor/Electronic unit Dimensions Height Variable speed 1.8 2.50 150 (polyolester) 300 870 4.3/0.25
S = Static cooling normally sufficient O = Oil cooling F1 = Fan cooling 1.5 m/s (compressor compartment temperature equal to ambient temperature) F2 = Fan cooling 3.0 m/s necessary SG = Suction gas cooling normally sufficent – = not applicable in this area
Ω cm3 cm3 g cm3 kg
Suction connector Process connector Discharge connector Connector tolerance
mm A 137 B 135 B1 128 B2 73 location/I.D. mm | angle C 6.2 | 41.5° location/I.D. mm | angle D 6.2 | 45° location/I.D. mm | angle E 5.0 | 21° I.D. mm ±0.09, on 5.0 +0.12/+0.20 24V cut-in [V] 24.2
204 170
78.5
ø16
Standard battery protection settings (no connection C - P) 12V cut-out [V] 12V cut-in [V] 24V cut-out [V] 10.4 11.7 22.8
Operational errors shown by LED (optional)
Number of flashes Error type
5
Thermal cut-out of electronic unit
(If the refrigeration system has been too hea vi ly loaded, or if the ambient tem pe ra ture is high, the electronic unit will run too hot).
In AEO (Adaptive Energy Optimizing) speed mode the BD compressor will always adapt its speed to the actual cooling demand.
Datasheet: DEHC.ED.100.E5.02 / November 2009
Accessories for BD50F Bolt joint for one compressor Ø: 16 mm Bolt joint in quantities Ø: 16 mm Snap-on in quantities Ø: 16 mm Remote kit (without cable) AC line cord (UL approved/VDE approved) DC usage: Std. automobile fuse12V: 15A / 24V: 7.5A Main switch: rated to min. 20A AC usage: Fuse 100-240V: 4A / Main switch: min. 6A
Not deliverable from Danfoss
November 2009
DEHC.PK.100.C9.02/520N0916
16
BD50F Direct Current Compressor (Inch Connectors), R134a, 12-24V DC & 100-240V AC 50/60Hz
Compressors Code number (without electronic units) Electronic unit 12-24V DC - standard Electronic unit 12-24V DC - with metal shielding Electronic unit 12-24V DC - with AEO Electronic unit 12-24V DC - with AEO & metal shielding Electronic unit 12-24V DC & 100-240V AC 50/60Hz Approved compressor - electronic unit combinations Additional approvals Compressors on pallet Application Application Evaporating temperature Voltage range (DC & AC) Max. condensing temperature continuous (short) Max. winding temperature continuous (short) 101Z0203 single: 101N0210, 30 pcs: 101N0211 single: 101N0220, 30 pcs: 101N0221 single: 101N0300, 30 pcs: 101N0301 single: 101N0320, 30 pcs: 101N0321 single: 101N0500, 36 pcs: 101N0501 refer to Technical Info DEHC.EI.100.C e4, C-Tick 150 LBP/MBP/HBP -20 to 50 12-24V DC & 100-240V AC 50/60Hz °F 140 (158) °F 257 (275) °F HBP F1 F1 F1 S = Static cooling normally sufficient O = Oil cooling F1 = Fan cooling 1.5 m/s (compressor compartment temperature equal to ambient temperature) F2 = Fan cooling 3.0 m/s necessary SG = Suction gas cooling normally sufficent – = not applicable in this area
Cooling requirements Application LBP MBP 32°C S S 38°C S S 43°C S S Remarks on application: Fan cooling F1 depending on application and speed. Motor Motor type Resistance, all 3 windings (25°C) Design Displacement Oil quantity (type) Maximum refrigerant charge Free gas volume in compressor Weight - Compressor/Electronic unit Dimensions Height Variable speed 1.8 0.15 5.1 (polyolester) 10.5 29.6 9.5/0.55
Ω cu.in. fl.oz. oz. fl.oz. lbs.
0.63"(16)
Suction connector Process connector Discharge connector
inch A B B1 B2 location/I.D. in. | angle C location/I.D. in. | angle D location/I.D. in | angle E
Operational errors shown by LED (optional)
Number of flashes Error type
5
Thermal cut-out of electronic unit
(If the refrigeration system has been too hea vi ly loaded, or if the ambient tem pe ra ture is high, the electronic unit will run too hot).
Test conditions Condensing temperature Ambient temperature Suction gas temperature Liquid temperature
ASHRAE 130°F 90°F 90°F 90°F
EN 12900/CECOMAF 131°F 90°F 90°F no subcooling Code number 118-1917 118-1918 118-1919 105N9210 105N9520/30 Not deliverable from Danfoss
In AEO (Adaptive Energy Optimizing) speed mode the BD compressor will always adapt its speed to the actual cooling demand.
Accessories for BD50F Bolt joint for one compressor Ø: 5/8 in. Bolt joint in quantities Ø: 5/8 in. Snap-on in quantities Ø: 5/8 in. Remote kit (without cable) AC line cord (UL approved/VDE approved) DC usage: Std. automobile fuse12V: 15A / 24V: 7.5A Main switch: rated to min. 20A AC usage: Fuse 100-240V: 4A / Main switch: min. 6A
Datasheet: DEHC.ED.100.M5.22 / November 2009
November 2009
DEHC.PK.100.C9.02/520N0916
18
BD80F Direct Current Compressor R134a, 12-24V
General Code number (without electronic units) Electronic unit (with integrated fan cooling) Approved compressor - electronic unit combinations Additional approvals Compressors on pallet Application Application Evaporating temperature Voltage range/max. voltage Max. condensing temperature continuous (short) Max. winding temperature continuous (short) Cooling requirements Application 32°C 38°C 43°C Remarks on application: Motor Motor type Resistance, all 3 windings (25°C) Design Displacement Oil quantity (type) Maximum refrigerant charge Free gas volume in compressor Weight - Compressor/Electronic unit Dimensions Height 101Z0280 single: 101N0290, 28 pcs: 101N0291 refer to Technical Info DEHC.EI.100.C e4, C-Tick 150 LBP -30 to -5 12-24/31.5 60 (70) 125 (135) LBP S S S MBP – – – HBP – – –
S = Static cooling normally sufficient O = Oil cooling F1 = Fan cooling 1.5 m/s (compressor compartment temperature equal to ambient temperature) F2 = Fan cooling 3.0 m/s necessary SG = Suction gas cooling normally sufficent – = not applicable in this area
Standard battery protection settings (no connection C - P) 12V cut-out [V] 12V cut-in [V] 24V cut-out [V] 10.4 11.7 22.8
Suction connector Process connector Discharge connector Connector tolerance
mm A 137 B 135 B1 128 B2 73 location/I.D. mm | angle C 6.2 | 41.5° location/I.D. mm | angle D 6.2 | 45° location/I.D. mm | angle E 5.0 | 21° I.D. mm ±0.09, on 5.0 +0.12/+0.20
Operational errors shown by LED (optional)
Number of flashes Error type
5
Thermal cut-out of electronic unit
(If the refrigeration system has been too hea vi ly loaded, or if the ambient tem pe ra ture is high, the electronic unit will run too hot).
0
12V DC static cooling watt 5 7.2 10 15
4
Minimum motor speed error
(If the refrigeration system is too heavily loaded, the motor cannot maintain minimum speed at approximately 2,450 rpm).
3
Motor start error
(The rotor is blocked or the differential pressure in the refrigeration system is too high (>5 bar)).
0
12V DC static cooling watt 5 7.2 10 15
2
Fan over-current cut-out
(The fan loads the electronic unit with more than 1Apeak).
Compressor speed Electronit unit Resistor (R1) [Ω] Code number calculated values 0 203 101N0290 451 with AEO 867 1700
Motor speed [rpm] AEO 2,500 3,100 3,800 4,400
Control circuit current [mA] 6 5 4 3 2
Test conditions Condensing temperature Ambient temperature Suction gas temperature Liquid temperature Accessories for Bolt joint for one compressor Bolt joint in quantities Snap-on in quantities Remote kit (without cable) Standard automoblie fuse DIN 7258 Main switch
EN 12900/CECOMAF 55°C 32°C 32°C no subcooling BD80F Ø: 16 mm Ø: 16 mm Ø: 16 mm 12V: 30A 24V: 15A rated to min. 30A
In AEO (Adaptive Energy Optimizing) speed mode the BD compressor will always adapt its speed to the actual cooling demand.
Not deliverable from Danfoss
Datasheet: DEHC.ED.100.A8.02 / November 2009
November 2009
DEHC.PK.100.C9.02/520N0916
20
BD250GH Direct Current Compressor R134a, 12-24V
General Code number (without electronic units) Electronic unit (with integrated fan cooling) Approved compressor - electronic unit combinations Additional approvals Compressors on pallet Application Application Evaporating temperature Voltage range/max. voltage Max. condensing temperature continuous (short) Max. winding temperature continuous (short) Cooling requirements Application 32°C 38°C 43°C Remarks on application: Motor Motor type Resistance, all 3 windings (25°C) Design Displacement Oil quantity (type) Maximum refrigerant charge Free gas volume in compressor Weight - Compressor/Electronic unit Dimensions Height 101Z0400 single: 101N0290, 28 pcs: 101N0291 refer to Technical Info DEHC.EI.100.C e4, C-Tick 150 LBP/MBP/HBP -25 to 15 12-24/31.5 60 (70) 125 (135) LBP S S S MBP S S S HBP S S S
S = Static cooling normally sufficient O = Oil cooling F1 = Fan cooling 1.5 m/s (compressor compartment temperature equal to ambient temperature) F2 = Fan cooling 3.0 m/s necessary SG = Suction gas cooling normally sufficent – = not applicable in this area
Standard battery protection settings (no connection C - P) 12V cut-out [V] 12V cut-in [V] 24V cut-out [V] 10.4 11.7 22.8
Suction connector Process connector Discharge connector Connector tolerance
mm A 137 B 135 B1 128 B2 73 location/I.D. mm | angle C 6.2 | 41.5° location/I.D. mm | angle D 6.2 | 45° location/I.D. mm | angle E 5.0 | 21° I.D. mm ±0.09, on 5.0 +0.12/+0.20
Operational errors shown by LED (optional)
Number of flashes Error type
5
Thermal cut-out of electronic unit
(If the refrigeration system has been too hea vi ly loaded, or if the ambient tem pe ra ture is high, the electronic unit will run too hot).
4
Minimum motor speed error
(If the refrigeration system is too heavily loaded, the motor cannot maintain minimum speed at approximately 2,450 rpm).
3
Motor start error
(The rotor is blocked or the differential pressure in the refrigeration system is too high (>5 bar)).
2
Fan over-current cut-out
(The fan loads the electronic unit with more than 1Apeak).
* Possible thermal cut-out of electronic unit due to heavy loaded refrigeration system.
Terminal plug Fuse Main switch
+
+ -
+
+ F D C P T
Power supply
LED R1
Fan
8540-2
Thermostat
R2
8583
105N9210
Compressor speed Electronit unit Resistor (R1) [Ω] Code number calculated values 0 203 101N0290 451 with AEO 867 1700
Motor speed [rpm] AEO 2,500 3,100 3,800 4,400
Control circuit current [mA] 6 5 4 3 2
Test conditions Condensing temperature Ambient temperature Suction gas temperature Liquid temperature Accessories for Bolt joint for one compressor Bolt joint in quantities Snap-on in quantities Remote kit (without cable) Standard automoblie fuse DIN 7258 Main switch
EN 12900/CECOMAF 55°C 32°C 32°C no subcooling BD250GH Ø: 16 mm Ø: 16 mm Ø: 16 mm 12V: 30A 24V: 15A rated to min. 30A
In AEO (Adaptive Energy Optimizing) speed mode the BD compressor will always adapt its speed to the actual cooling demand.
Not deliverable from Danfoss
Datasheet: DEHC.ED.100.C6.02 / November 2009
November 2009
DEHC.PK.100.C9.02/520N0916
22
BD250/250GH Direct Current Twin Compressor R134a, 12-24V
General Code number (without electronic units) 101Z0500 Electronic unit (with integrated fan cooling, 2 pcs. required) single: 101N0290, 28 pcs: 101N0291 Remote kit (2 pcs. required) 105N9210 (without cable) Approved compressor - electronic unit combinations refer to Technical Info DEHC.EI.100.C Additional approvals e4, C-Tick Compressors on pallet 40 Application Application Evaporating temperature Voltage range/max. voltage Max. condensing temperature continuous (short) Max. winding temperature continuous (short) Cooling requirements Application 32°C 38°C 43°C Remarks on application: Motor Motor type Resistance, all 3 windings (25°C) Design Displacement Oil quantity (type) Maximum refrigerant charge Free gas volume in compressor Weight - Compressor/Electronic unit Dimensions Height LBP/MBP/HBP -25 to 15 12-24/31.5 60 (70) 125 (135) LBP S S S MBP S S S HBP S S S
°C VDC °C °C
S = Static cooling normally sufficient O = Oil cooling F1 = Fan cooling 1.5 m/s (compressor compartment temperature equal to ambient temperature) F2 = Fan cooling 3.0 m/s necessary SG = Suction gas cooling normally sufficent – = not applicable in this area
Ω cm3 cm3 g cm3 kg
Variable speed 1.8 2 x 2.50 400 (polyolester) 600 2 x 870 8.8/2 x 0.3
Suction connector Process connector Discharge connector Connector tolerance
mm A 137 B 135 B1 128 B2 73 location/I.D. mm | angle C 6.2 | 41.5° location/I.D. mm | angle D 6.2 | 45° location/I.D. mm | angle E 5.0 | 21° I.D. mm ±0.09, on 5.0 +0.12/+0.20 24V cut-in [V] 24.2
8583-2
105N9210
ø16
ø4.2
204 170
70
140.5 388
8577
Standard battery protection settings (no connection C - P) 12V cut-out [V] 12V cut-in [V] 24V cut-out [V] 10.4 11.7 22.8
Operational errors shown by LED (optional)
Number of flashes Error type
5
Thermal cut-out of electronic unit
(If the refrigeration system has been too hea vi ly loaded, or if the ambient tem pe ra ture is high, the electronic unit will run too hot).
4
Minimum motor speed error
(If the refrigeration system is too heavily loaded, the motor cannot maintain minimum speed at approximately 2,450 rpm).
3
Motor start error
(The rotor is blocked or the differential pressure in the refrigeration system is too high (>5 bar)).
2
Fan over-current cut-out
(The fan loads the electronic unit with more than 1Apeak).
* Possible thermal cut-out of electronic unit due to heavy loaded refrigeration system.
Fuse Fuse
Main switch Main switch Main switch
– – + +
Fuse
+
+ -
+
+ F D C P T
+
+ F D C P T
Power supply
+
+ -
+
+ F D C P T
Fuse
+
+ F D C P T
Power supply
LED R3
Fan
LED R3 Thermostat R1
Fan
Thermostat
R2
R2
R1
R3 = 47 - 68 Ω
R3 = 47 - 68 Ω
8576-2 8576
R3 R1
R2
R3 R1
R2
Compressor speed Electronit unit Resistor (R1) [Ω] Code number calculated values 0 203 101N0290 451 with AEO 867 1700
Motor speed [rpm] AEO 2,500 3,100 3,800 4,400
Control circuit current [mA] 6 5 4 3 2
Test conditions Condensing temperature Ambient temperature Suction gas temperature Liquid temperature Accessories for Bolt joint for one compressor Bolt joint in quantities Snap-on in quantities Standard automoblie fuse DIN 7258 Main switch
EN 12900/CECOMAF 55°C 32°C 32°C no subcooling BD250/250GH Ø: 16 mm Ø: 16 mm Ø: 16 mm 12V: 30A 24V: 15A rated to min. 30A
ASHRAE 54.4°C 32°C 32°C 32°C Code number 118-1900 118-1901 118-1902
In AEO (Adaptive Energy Optimizing) speed mode the BD compressor will always adapt its speed to the actual cooling demand.
Not deliverable from Danfoss
Datasheet: DEHC.ED.100.B6.02 / November 2009
November 2009
DEHC.PK.100.C9.02/520N0916
24
BD35K Direct Current Compressor for Solar Applications (for stationary use only), R600a , 10-45V
General Code number (without electronic units) Electronic unit 10-45V - for solar applications Electronic unit 12-24V DC - standard Electronic unit 12-24V DC - with metal shielding Approved compressor - electronic unit combinations Additional approvals Compressors on pallet Application Application Evaporating temperature Voltage range Max. condensing temperature continuous (short) Max. winding temperature continuous (short) Cooling requirements Application 32°C 38°C 43°C LBP S S S MBP S S S HBP S S S °C VDC °C °C LBP/MBP/(HBP) -30 to 0 (10) 10-45 60 (70) 125 (135) 101Z0211 single: 101N0400, 30 pcs: 101N0401 single: 101N0210, 30 pcs: 101N0211 single: 101N0220, 30 pcs: 101N0221 refer to Technical Info DEHC.EI.100.C e4 150 S = Static cooling normally sufficient O = Oil cooling F1 = Fan cooling 1.5 m/s (compressor compartment temperature equal to ambient temperature) F2 = Fan cooling 3.0 m/s necessary SG = Suction gas cooling normally sufficent – = not applicable in this area
Remarks on application: Fan cooling F1 depending on application and speed.
Motor Motor type Resistance, all 3 windings (25°C) Design Ω Variable speed 1.8
204 170
78.5
Displacement Oil quantity (type) Maximum refrigerant charge Free gas volume in compressor Weight - Compressor/Electronic unit Dimensions Height
cm3 cm3 g cm
3
3.00 150 (polyolester) 120 870 4.3/0.25
kg
ø16
D
ø4.2
127
C
mm A B B1 B2
137 135 73 6.2 | 41.5° Cu-plated steel | Al caps 6.2 | 45° Cu-plated steel | Al caps 5.0 | 21° Cu-plated steel | Al caps 128
120
B1 B A B2
material | comment Process connector Discharge connector Oil cooler connector Connector tolerance Remarks: location/I.D. mm | angle D material | comment location/I.D. mm | angle E material | comment location/I.D. mm | angle F material | comment I.D. mm
Operational errors shown by LED (optional)
Number of flashes Error type
5
Thermal cut-out of electronic unit
(If the refrigeration system has been too hea vi ly loaded, or if the ambient tem pe ra ture is high, the electronic unit will run too hot).
Test conditions Condensing temperature Ambient temperature Suction gas temperature Liquid temperature Accessories for Bolt joint for one compressor Bolt joint in quantities Snap-on in quantities Remote kit (without cable) Standard automoblie fuse DIN 7258 Main switch
EN 12900/CECOMAF 55°C 32°C 32°C no subcooling BD35K Ø: 16 mm Ø: 16 mm Ø: 16 mm 12V: 30A 24V: 15A rated to min. 30A
In AEO (Adaptive Energy Optimizing) speed mode the BD compressor will always adapt its speed to the actual cooling demand.
Datasheet: DEHC.ED.100.G5.02 / November 2009
Not deliverable from Danfoss
November 2009
DEHC.PK.100.C9.02/520N0916
26
BD100CN Direct Current Compressor (for stationary use only), R290, 12-24V
General Code number (without electronic units) Electronic unit (with integrated fan cooling) Approved compressor - electronic unit combinations Additional approvals Compressors on pallet Application Application Evaporating temperature Voltage range/max. voltage Max. condensing temperature continuous (short) Max. winding temperature continuous (short) Cooling requirements Application 32°C 38°C 43°C Remarks on application: Motor Motor type Resistance, all 3 windings (25°C) Design Displacement Oil quantity (type) Maximum refrigerant charge Free gas volume in compressor Weight - Compressor/Electronic unit Dimensions Height 101Z0401 single: 101N0290, 28 pcs: 101N0291 refer to Technical Info DEHC.EI.100.C e4, C-Tick 150 LBP -40 to -10 12-24/31.5 55 (65) 125 (135) LBP S S S MBP – – – HBP – – –
S = Static cooling normally sufficient O = Oil cooling F1 = Fan cooling 1.5 m/s (compressor compartment temperature equal to ambient temperature) F2 = Fan cooling 3.0 m/s necessary SG = Suction gas cooling normally sufficent – = not applicable in this area
Standard battery protection settings (no connection C - P) 12V cut-out [V] 12V cut-in [V] 24V cut-out [V] 10.4 11.7 22.8
Suction connector Process connector Discharge connector Connector tolerance
mm A 137 B 135 B1 128 B2 73 location/I.D. mm | angle C 6.2 | 41.5° location/I.D. mm | angle D 6.2 | 45° location/I.D. mm | angle E 5.0 | 21° I.D. mm ±0.09, on 5.0 +0.12/+0.20
Operational errors shown by LED (optional)
Number of flashes Error type
5
Thermal cut-out of electronic unit
(If the refrigeration system has been too hea vi ly loaded, or if the ambient tem pe ra ture is high, the electronic unit will run too hot).
12V DC static cooling watt -5 0 5 7.2
4
Minimum motor speed error
(If the refrigeration system is too heavily loaded, the motor cannot maintain minimum speed at approximately 2,450 rpm).
3
Motor start error
(The rotor is blocked or the differential pressure in the refrigeration system is too high (>5 bar)).
12V DC static cooling watt -5 0 5 7.2
2
Fan over-current cut-out
(The fan loads the electronic unit with more than 1Apeak).
Compressor speed Electronit unit Resistor (R1) [Ω] Code number calculated values 0 203 101N0290 451 with AEO 867 1700
Motor speed [rpm] AEO 2,500 3,100 3,800 4,400
Control circuit current [mA] 6 5 4 3 2
Test conditions Condensing temperature Ambient temperature Suction gas temperature Liquid temperature Accessories for Bolt joint for one compressor Bolt joint in quantities Snap-on in quantities Remote kit (without cable) Standard automoblie fuse DIN 7258 Main switch
EN 12900/CECOMAF* 45°C 32°C 32°C no subcooling BD100CN Ø: 16 mm Ø: 16 mm Ø: 16 mm 12V: 30A 24V: 15A rated to min. 30A
ASHRAE* 45°C 32°C 32°C 32°C
In AEO (Adaptive Energy Optimizing) speed mode the BD compressor will always adapt its speed to the actual cooling demand.
Code number 118-1917 118-1918 118-1919 105N9210 Not deliverable from Danfoss
Datasheet: DEHC.ED.100.H5.02 / November 2009
November 2009
DEHC.PK.100.C9.02/520N0916
28
Remote Kit for BD Compressors I.
Packages Single Pack I - Pack
with cable 105N9100
excl. cable 105N9210 105N9200, 80 pcs.
bracket, cover, 750 mm cable with two plugs bracket, cover, two plugs
!
II. IV.
V.
!
III.
! !
VI.
!
!
!
!
!
AC Line Cord for BD Electronic Unit 101N0500
!
Packages Single Pack I - Pack
US Version (UL) 105N9520 105N9521, 80 pcs
EU Version (VDE) 105N9530 105N9531, 80 pcs.
50 mm 1500 mm
29
DEHC.PK.100.C9.02/520N0916
November 2009
Code Numbers BD35/50/80F - BD35K - BD100CN - BD250GH
Compressors BD35F mm standard BD35F inch BD35K (R600a) BD50F mm BD50F inch BD80F mm BD250GH BD250GH Twin BD100CN (R290) Code number 101Z0200 101Z0204 101Z0211 101Z1220 101Z0203 101Z0280 101Z0400 101Z0500 101Z0401 Description standard compressor, mm tube connectors same as 101Z0200, inch tube connectors for stationary use only, mainly solar applications, mm tube connectors standard compressor, mm tube connectors same as 101Z1220, inch tube connectors standard compressor, mm tube connectors mm tube connectors, HBP compressor mm tube connectors, HBP compressor mm tube connectors, LBP compressor Description for BD35F/BD50F, speed setting, battery protection for BD35F/BD50F, radiation extra shielded, speed setting, battery protection for BD35F/BD50F, radiation extra shielded, conduction extra filtered, speed setting, battery protection for BD35F/BD50F, Adaptive Energy Optimization, speed setting, battery protection for BD35F/BD50F, Adaptive Energy Optimization, radiation extra shielded, speed setting, battery protection for BD35F/BD35K, optimized for direct solar panel operation, speed setting for BD35F/BD50F, speed setting, battery protection, integrated AC/DC converter for BD50F only, extra high start performance, speed setting, battery protection for BD80F/BD250GH/etc., Adaptive Energy Optimization, speed setting, battery protection for BD35F, CISPR 25 class 5 approved, speed setting, battery protection, lamp output for BD35F, CISPR 25 class 5 approved, speed setting, battery protection, lamp output bracket, cover, 750 mm cable with two plugs bracket, cover, two plugs for electronic unit with AC/DC converter for electronic unit with AC/DC converter Description for BD35F/BD50F, speed setting, battery protection, 30 pcs. for BD35F/BD50F, radiation extra shielded, speed setting, battery protection, 30 pcs. for BD35F/BD50F, Adaptive Energy Optimization, speed setting, battery protection, 30 pcs. for BD35F/BD50F, Adaptive Energy Optimization, radiation extra shielded, speed setting, bat. prot., 30 pcs. for BD35F/BD35K, optimized for direct solar panel operation, speed setting, 30 pcs. for BD35F/BD50F, speed setting, battery protection, integrated AC/DC converter, 36 pcs. for BD50F only, extra high start performance, speed setting, battery protection, 30 pcs. for BD80F/BD250GH/etc., Adaptive Energy Optimization, speed setting, battery protection, 28 pcs. for BD35F, CISPR 25 class 5 approved, speed setting, battery protection, lamp output, 30 pcs. for BD35F, CISPR 25 class 5 approved, speed setting, battery protection, lamp output, 30 pcs. bracket, cover and two plugs, 200 pcs. for electronic unit with AC/DC converter, 80 pcs. for electronic unit with AC/DC converter, 80 pcs. Remote kit, parts (cable assembly not shown) AC line cord, single packs
Electronic Single Pack Code number Electronic standard 101N0210 Electronic EMI 101N0220 Electronic extended EMI 101N0900 Electronic AEO 101N0300 Electronic AEO with EMI 101N0320 Electronic solar 101N0400 Electronic w. AC/DC converter 101N0500 Electronic BD50F high start 101N0230 Electronic high speed 101N0290 Electronic automotive 101N0600 Electronic automotive (connector) 101N0630 Remote kit with cable 105N9100 Remote kit without cable 105N9210 AC line cord (UL approved) 105N9520 AC line cord (VDE approved) 105N9530 Electronic I - Pack Code number Electronic standard 101N0211 Electronic EMI 101N0221 Electronic AEO 101N0301 Electronic AEO with EMI 101N0321 Electronic solar 101N0401 Electronic w. AC/DC converter 101N0501 Electronic BD50F high start 101N0231 Electronic high speed 101N0291 Electronic automotive 101N0601 Electronic automotive (connector) 101N0631 Remote kit without cable 105N9200 AC line cord (UL approved) 105N9521 AC line cord (VDE approved) 105N9531
Accessories
Remote kit, mounted
AC line cord UL/VDE approved versions
Electronic unit with AC/DC converter with L-N socket for AC line cord
AC line cord, AC plug
November 2009
DEHC.PK.100.C9.02/520N0916
30
BD100CN R290, -40°C, -10°C evap. temp. Stationary freezer application (not approved for vehicles), solar-powered systems, ice cream boxes up to 200 l, pharmaceutical applications, 30-210 W cooling capacity. BD35K R600a, -30°C, +10°C evap. temp. Stationary application, solar-powered vaccine coolers etc., 100-200 l coolers, 15-120 W cooling capacity.
BD250GH Single or Twin Configuration R134a, -25°C, +15°C evap. temp. Designed for cabin cooling in trucks during nighttime, very silent operation, 80-420 W single cooling capacity.
BD35F Multivoltage R134a, -30°C, +10°C evap. temp. All mobile applications for portable boxes, boats, trucks etc., can be powered with AC and DC, 85-265 V AC 50/60 Hz, 1224 V DC, automatic selection of AC when available, 15-120 W cooling capacity BD35F/50F/80F Basic R134a, -30°C, +10°C evap. temp. All mobile applications for portable boxes, boats, trucks etc., 15-140/20190/35-220 W cooling capacity.
BD35F with EMI Electronic R134a, -30°C, +10°C evap. temp. Designed for boats and trucks if risk of electric interference with radio or other electrical equipment, 15-150 W cooling capacity.
BD150F R134a, -35°C, -10°C evap. temp. The BD150F compressor is intended especially for the use in mobile applications, e.g. in vans and small trucks, 50-340 W cooling capacity.
BD350GH Single or Twin Configuration R134a, -25°C, +15°C evap. temp. Tailored for spotcooling systems in sleeping compartments in trucks, caravans, golf buggies etc., 85-780 W single cooling capacity
BD compressors bring comfort at work and leisure
Modern comfort is brought into life when leaving home. As people go mobile, so does food. The excellent performance of the BD series safeguards food preservation. With our outstanding DC compressors for cars, vans, boats, trucks, etc., Danfoss has transcended the barriers for mobile refrigeration. The direct current compressors BD35F/50F/80F for 12/24 V DC power supply can be used in mobile refrigerators and freezers with refrigerant R134a. The BD250GH compressors for 12/24 V DC and the BD350GH compressors in 12 or 24 V DC versions are R134a HBP compressors used for mobile spot cooling systems. BD35K and BD100CN compressors can be used with HFC-free refrigerants in stationary applications. All compressors are equipped with an electronic unit with built-in thermal protection which also protects against destructive battery discharge.
Danfoss Compressors GmbH • Mads-Clausen-Str. 7 • D-24939 Flensburg / Germany • Tel: +49 (0461) 4941-0 • Fax: +49 (0461) 44715 • compressors.danfoss.com
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed. All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved
DEHC.PK.100.C9.02/520N0916
compressors.danfoss.com
(Produced by Danfoss Compressors/DEHC6093, 11.2009)